Paste an EzyStrut or Øglænd description. Compare the requested dimensions with the nearest options in the supplied Treadwell handover, then review the candidate part code.
Works with EzyStrut item descriptions/codes (e.g. N4L300FRP Cable ladder (6m), 46FA12-300-6000) or Øglænd System FOE type descriptions (e.g. FOE-150 CL-300-6000, FOE-150 FE-90-300 R600). Try an example, or paste your own.
Auto-detected fields are pre-filled — adjust anything that isn't right, or fill in manually for products the detector doesn't recognise.
Review size differences and assumptions before using this candidate in your BOM. Availability and performance are not verified.
Detect a description, review the fields and generate a candidate.
Nearest means the smallest dimension difference, which may be larger or smaller. Ties select the smaller size. Use the dropdowns to choose an alternative.
| Product | Code pattern |
|---|---|
| Straight cable ladder | EXD-CL-C(RailHeight)(Width)-(RungType)(RungSpacing)-(Resin)(Colour)-(Length) |
| Flat / Peaked cover | EXD-CL-FC or PC(Width)-(Resin)(Colour)-(Length) |
| Fitting (Tee / Bend / Cross / Riser) | EXD-CLF-(FittingType)(Angle)-C(RailHeight)(Width)(RungType)(Radius)-(Resin)(Colour) |
| Concentric bend (600mm radius only) | EXD-CLF-(FittingType)(Angle)-M(RailHeight)(Width)(RungType)600-(Resin)(Colour) |
| Reducer (straight/left/right) | EXD-CLR-(S/L/R)C(RailHeight)(W1)(W2)(RungType)-(Resin)(Colour) |
| Splice plate | EXD-CLP-(PlateType)-(RailHeight)(Angle)-(Material)(Colour) |
| Cover hold-down clamp | EXD-CLA-CH(RailHeight)-316 |
| Hold down clamp (ladder-to-support) | EXD-CLA-HDC (single generic code) |
| EXduro™ Strut channel nut | EXD-DSA-CN(RodSize) |
| EXsemble® threaded rod | EXS-R(Size)-V — stocked 1.2m / 2.4m lengths |
| EXsemble® hex flange nut | EXS-N(Size)-V |
| EXsemble® extra-large flat washer | EXS-W(Size)R-V |
Rail height (H): 50 / 75 / 100 / 150 / 200mm — 150mm is the handover default; this does not establish a NEMA load-class equivalence. Widths: 150–900mm. Rung spacing: 150 / 250 / 300 / 450mm (450 not available on 750/900mm widths). Resin: I-Series® Isophthalic (I, general purpose, commonly stocked) / V-Series® Vinyl Ester (V, highest chemical resistance) / P-Series® Phenolic (P, low smoke/fire critical). Colour: Light Grey (LG, commonly stocked) / Dark Grey (DG) / Custom (CC). Fitting-cover and reducer-cover exact code syntax was not fully spelled out in the 2025.6 guide — codes generated for those are best-effort reconstructions; confirm with Treadwell before ordering.
| Product | Type description pattern |
|---|---|
| Straight cable ladder | FOE-(RailHeight) CL-(Width)-(Length mm) |
| Flat Elbow / bend | FOE-(RailHeight) FE-(Angle)-(Width) R(Radius) |
| Tee-Piece | FOE-(RailHeight) TE-(Width)/(Width) R(Radius) |
| Cross-Piece | FOE-(RailHeight) CP-(Width)/(Width) R(Radius) |
| Inside / Outside Riser | FOE-(RailHeight) RI-IN/OU-90-(Width) R(Radius) |
| Reducer | FOE-(RailHeight) RE-L/R/Central-(Width)/(Width) |
| Splice Connector | FOE-(RailHeight) SC (bolt count)×M(size) |
| Splice Angle Plate | FOE-(RailHeight) SA-HO/VE-(Angle) (bolt count)×M(size) |
Rail heights: 70 / 100 / 150mm. Widths: 150 / 200 / 300 / 400 / 450 / 500 / 600 / 750 / 900mm (200/400/500 have no exact EXduro™ equivalent and get rounded to the nearest standard width — check this matters for your job). Radii: 300 / 600mm for horizontal fittings, 400 / 600 / 800mm for risers. This scheme was pulled from an automated summary of Øglænd's FRP catalogue PDF, not verified page-by-page (the original guides are not embedded in this handover) — treat exact punctuation and segment order as indicative, and confirm against Øglænd's own documentation before relying on it for anything order-critical. Øglænd's actual orderable part is a separate numeric article number, which this tool does not attempt to produce.